To main content

How to avoid unstable time domain responses caused by transformer models

Abstract

Modeling a three-winding transformer gives occasionally a negative reactance that may result in an unstable circuit. This unstable condition can be eliminated by neglecting the magnetizing losses or taking them into account in a different way as shown in this paper. Unstable responses are, under certain conditions, extremely dependent on the time step when using EMTP or similar programs. This paper shows why simulated terminal voltages do not always reveal an unstable circuit condition. Copyright IEEE

Category

Academic article

Language

English

Author(s)

  • Thor Birger Henriksen

Affiliation

  • SINTEF Energy Research / Energisystemer

Year

2002

Published in

IEEE Transactions on Power Delivery

ISSN

0885-8977

Volume

17

Issue

2

Page(s)

516 - 522

View this publication at Cristin