To main content

Surface charging of dielectric barriers under positive lightning impulse stress

Abstract

The complex geometry of gas-insulated substations makes it difficult to predict withstand voltages. A key challenge is the characterization of the interaction between electrical discharges and dielectric surfaces. A 60 mm rod-plane air gap with a dielectric barrier is stressed with positive lightning impulse, initiating discharges that are characterized with a PMT, a current measurement system and a high-speed camera. The discharges do not lead to breakdown at the tested voltages. The residual potential on the barrier is measured with a potential probe. Depending on the gap distance, the potential distribution is either bell-shaped or saddle-shaped. The saddle-shape appears when back discharges are seen from the electrode to the barrier. Back discharges reduce the surface charge until the voltage between barrier and rod is lower than the rod inception voltage. Charge density distributions are estimated from the measurements using FEM simulations. In addition to streamer discharges, leader-type channels are sometimes observed. They are arrested close to the dielectric surface. Streamers from these channels charge the dielectric barrier additionally.
Read publication

Category

Academic chapter/article/Conference paper

Client

  • Research Council of Norway (RCN) / 245422

Language

English

Author(s)

Affiliation

  • Norwegian University of Science and Technology
  • SINTEF Energy Research / Elkraftteknologi

Year

2017

Publisher

IEEE

Book

2017 Annual Conference on Electric Insulation and Dielectric Phenomena - CEIDP 2017

Issue

2017

ISBN

978-1-5386-1194-4

Page(s)

802 - 806

View this publication at Cristin